Prod Model: |
EX1K~EX3KL |
Markets: |
North America,South America,Eastern Europe,Southeast Asia,Africa,Oceania,Mid East,Eastern Asia,Western Europe |
UPS Logo: |
Zlpower |
UPS Communications: |
Db-9 Connector: RS232 Serial Interface; Power Moni |
Intelligent Slot Snmp: |
Power Management From Snmp Manager |
UPS Network Surge Protection: |
RJ45 I/O Port Available for 10base -T Network or F |
UPS Recharge Time: |
5hours to 90% of Full Capacity After Full Load Dis |
Overload Capability For UPS: |
108%-150% for 30sec: ≥ 150% for 200ms |
Input UPS Power Factor: |
>0.97 |
Power Factor: |
0.7/0.8 |
AC Mode Efficiency: |
85% |
Battery Mode Efficiency: |
83% |
Phase: |
Single Phase |
Type: |
On-line |
Protection: |
Fully Protection for UPS and Device |
Product Description
High frequency online UPS EX1K, EX2K, EX3K is LCD digital display double conversion uninterruptible power supply, pure sine wave output wave form.
There are two models, one is standard online UPS with inside batteries such as EX1K, the other is long backup time online UPS without batteries such as EX1KL, will backup long time after connecting with external battery banks.
Application:
Servers, sensitive electronic equipment, telecom, bank, bureau, office, home, ATM, traffic, hospital, public security and so on.
Main Features:
1. Large blue ground LCD digital display shows Detailed Real-Time UPS Status and parameters.
2. Set Output voltage, Frequency parameter and bypass function on the display.
3. Advanced MCU microprocessor control technology, ensure long life reliability. 4. Wide input voltage range, Zero transfer time.
5. Excellent Protection against over voltage, over load, over current, over charge and so on.
6. Input L and N lines reverse wiring detection, Auto start when AC back.
7. DC start function, Input PFC revise function.
8. Humanization bypass output can be adjustable.
9. Smart RS232 communication with monitoring software.
10. Intelligent slot available for AS-400 Dry contact and SNMP card Remote control.
11. Strong antijamming capability.
12. Available to work with generators.
13. Lightning, surge, short circuit, Network/fax/modem surge protection.
14. Corresponding plug and sockets to different countries.
UPS Model | EX1K | EX1KL | EX2K | EX2KL | EX3K | EX3KL |
Capacity | 1000VA/700W | 2000VA/1400W | 3000VA/2100W |
Input | Voltage | (115~300) VAC |
Frequency | 46~54Hz/56~64Hz (Adjustable via LCD panel) |
Output | Voltage | 220/230/240 (1±1%)VAC (Adjustable via LCD panel) |
Frequency | 50/60Hz (Adjustable via LCD panel) 50Hz AC Mode: Follow AC Mode (AC Range 46~54Hz); Battery Mode: 50Hz (1±0.2%) 60Hz AC Mode: Follow AC Mode (AC Range56~64Hz); Battery Mode: 60Hz (1±0.2%) |
Output Wave Form | Sine Wave |
UPS Back-up Time | Full Load | ≥5′ | Depends on the capacity of the external battery bank | ≥9′ | Depends on the capacity of the external battery bank | ≥5′ | Depends on the capacity of the external battery bank |
Half Load | ≥14′ | ≥21′ | ≥15′ |
Battery Nominal DC Voltage | 36VDC | 96VDC |
Transfer Time | 0ms |
Overload Capacity | 110%~150% maintain 30s then turn to bypass output, over 150% maintain 300ms |
Communications | RS-232+Intelligent Slot |
Environment | Temperature | 0C~40C |
Humidity | 15%~90% |
Dimensions (W*D*H) mm | 145*400*220 | 192*460*340 |